RS485 - Industrial Parts & Components
Part List
- In running status,press Shift to show different displays among running
frequency,output current,output voltage, temperature,set pressure and
running pressure
Used to start,stop pump and for reset fault.The button is invalid when the external
terminal is connected. Used to save parameters settings
Reset (back to factory default setting) by pressing and
simultaneously
How to set parameters
The system has two parameter group: 1. U group (function group) ,U group includes U0,U1,U2,U3
subgroups 2. d group (monitoring group)
1) At the original display status, press SHIFT to display sequently running frequency,output current,dc link voltage,temperature and set pressure-current presure. 2) At the orignal displaly status, press MENU and hold for 3 seconds to enter U group ,press MENU
again (do not need to hold for 3secs) to switch to d group
Press MENU for 3 times to return to original display status. 3) After entering U group,press “+” to enter U1.U2.U3 group. Press ENTER to the function code,press
ENTER again to the parameter of the function code, press “+ “and “- “ to modify the parameter and
press ENTER to save the setting.finally press MENU continually for 3 times to return to the original
display status
4) Under stop/running status, press “+” / “-” and hold 3seconds to increase or decrease pressure
The following is the procedure on how to change the sensor range (U0-04)
from 10bar (factory default value) to 15bar. The procedure is the same for
setting other parameters.
6 / 21
7 / 21
Single pump control mode
1.Terminal wiring diagram
2.Debugging procedure - Quick operation step
1) Target pressure setting
At Stop/running status, directly press or ( do not need to enter U
parameter group) and hold for 3 seconds,then set the target pressure.. 2) Basic parameters setting
Note: “○” means parameters can be modified at both stop and running status. “●” means parameters can be modified only at stop status. Function
Code
Description Set range Unit Default Modification
Level Note
U0-02 Running
Direction
0:Forward
1:Reverse
2: Forbidden
0 ○ U0-03 Sensor type
0: (0-10)
1: (4-20)
5: (4-20)
V
mA
mA
1 ●
0: V termial
1: C termial
5: C1 terminal
U0-04 Sensor Range 0.0-60 Bar 10 ○
8 / 21
U0-05 Press. Calibration
(0~2.000) 1.000 ○ Below is parameters needed to set based on user’s requirement
Function
Code
Description Set range Unit Default Modification
Level
Note
U0-01 Start Press. Setting
0-target press. Bar 2.4 ○
80% of target
press. U1-05 High Press. Alarm Value
0-60.0 Bar 15.0 ○ U1-07
Low Press. Alarm Value
0-60.0 Bar 0.5 ○ U0-10
Start and
Stop
command
0:keypad
1:External
control
2:Communicati
on
0 ○ When use
external switch
on/off, set U0-10=1
Multi-pump control - Terminal wiring diagram
In two master and multi slave pumping system,master and standby master drive are connected to
pressure sensors as below:
1)Multi-Pump Control-Can realize two masters and Max.4 auxiliaries (standby master works as slave) to
combine work.
When display
smaller than
gauge,increas e U0-05. When display
bigger than
gauge,decreas e U0-05
9 / 21
2)There are two masters (one is master,the other is standby master) and 3 slaves. The standby master
replaces the master to command the whole system only when the master fails to work.The two master
drives are both equipped with pressure transducers,the other auxiliary drives are without transducers. 3).All the drives are connected through a RS485 Communication line. 4) The master detects pipe water pressure through pressure transducer,and sends the pressure signal
to the auxiliaries and automatically controls the auxiliaries to run or stop and PID status according to
the water pressure condition. 5) When master drive failes to work, the standby master will automatically replace the master to controls
the whole system; when any auxiliary drive fails to work, the system will just skip it by and start the next
one, ensuring the automatic shift of pump group. 6) The pumps run alternately (8hours by default) to balance every pump’s running time to prolong
service life of the whole unit machine. 2. Operating steps for multi-pump system
1) Set target pressure on master drive
At Stop status, directly press or ( do not need to enter U parameter group)
and hold for 3 seconds,then set the target pressure.. 2)Set sensor type and sensor range on master and standby drive. Function
Code
Description Set range Unit Default Modification
Level Note
U0-03 Sensor type
0: (0-10)
1: (4-20)
5: (4-20)
V
mA
mA
1 ●
0: V termial
1: C termial
5: C1 terminal
U0-04 Sensor Range 0.0-60 Bar 10 ○ 3)Confirm each pump’s rotation direction
If any pump’s rotation direction is not correct, refer to one of the following 2 ways to change the the
rotation direction:
a. Modify U0-02 value
b. Exchange any two of U/V/W wiring
4)Adjust display pressure
When display smaller than gauge,increase U0-05.When display bigger than gauge,decrease U0-05
5)Parameters setting for pumping system
Two pump system :
Drive type Parameters setting
Master drive 1 U3-03=2, Standby drive 2 U0-10=2,U0-13=2,U3-01=2
10 / 21
Three pump system:
Drive type Parameters setting
Master drive 1 U3-03=2
Standby drive 2 U0-10=2,U0-13=2,U3-01=2,U3-03=2
Slave drive 3 U0-10=2,U0-13=2,U3-01=3
Four pump system:
Drive type Parameters setting
Master drive 1 U3-03=3
Standby drive 2 U0-10=2,U0-13=2,U3-01=2,U3-03=3
Slave drive 3 U0-10=2,U0-13=2,U3-01=3
Slave drive 4 U0-10=2,U0-13=2,U3-01=4
Five pump system:
Drive type Parameters setting
Master drive 1 U3-03=4
Standby drive 2 U0-10=2,U0-13=2,U3-01=2,U3-03=3
Slave drive 3 U0-10=2,U0-13=2,U3-01=3
Slave drive 4 U0-10=2,U0-13=2,U3-01=4
Slave drive 5 U0-10=2,U0-13=2,U3-01=5
Note: The screen display on standby and slave drives are running frequency (default setting)
Terminal instruction
Terminal Name Description
DI1,DI2,D3