Part List

  1. In running status,press Shift to show different displays among running
    frequency,output current,output voltage, temperature,set pressure and
    running pressure
    Used to start,stop pump and for reset fault.The button is invalid when the external
    terminal is connected. Used to save parameters settings
    Reset (back to factory default setting) by pressing and
    simultaneously
    How to set parameters
    The system has two parameter group: 1. U group (function group) ,U group includes U0,U1,U2,U3
    subgroups 2. d group (monitoring group)
    1) At the original display status, press SHIFT to display sequently running frequency,output current,dc link voltage,temperature and set pressure-current presure. 2) At the orignal displaly status, press MENU and hold for 3 seconds to enter U group ,press MENU
    again (do not need to hold for 3secs) to switch to d group
    Press MENU for 3 times to return to original display status. 3) After entering U group,press “+” to enter U1.U2.U3 group. Press ENTER to the function code,press
    ENTER again to the parameter of the function code, press “+ “and “- “ to modify the parameter and
    press ENTER to save the setting.finally press MENU continually for 3 times to return to the original
    display status
    4) Under stop/running status, press “+” / “-” and hold 3seconds to increase or decrease pressure
    The following is the procedure on how to change the sensor range (U0-04)
    from 10bar (factory default value) to 15bar. The procedure is the same for
    setting other parameters.
    6 / 21
    7 / 21
    Single pump control mode
    1.Terminal wiring diagram
    2.Debugging procedure
  2. Quick operation step
    1) Target pressure setting
    At Stop/running status, directly press or ( do not need to enter U
    parameter group) and hold for 3 seconds,then set the target pressure.. 2) Basic parameters setting
    Note: “○” means parameters can be modified at both stop and running status. “●” means parameters can be modified only at stop status. Function
    Code
    Description Set range Unit Default Modification
    Level Note
    U0-02 Running
    Direction
    0:Forward
    1:Reverse
    2: Forbidden
    0 ○ U0-03 Sensor type
    0: (0-10)
    1: (4-20)
    5: (4-20)
    V
    mA
    mA
    1 ●
    0: V termial
    1: C termial
    5: C1 terminal
    U0-04 Sensor Range 0.0-60 Bar 10 ○
    8 / 21
    U0-05 Press. Calibration
    (0~2.000) 1.000 ○ Below is parameters needed to set based on user’s requirement
    Function
    Code
    Description Set range Unit Default Modification
    Level
    Note
    U0-01 Start Press. Setting
    0-target press. Bar 2.4 ○
    80% of target
    press. U1-05 High Press. Alarm Value
    0-60.0 Bar 15.0 ○ U1-07
    Low Press. Alarm Value
    0-60.0 Bar 0.5 ○ U0-10
    Start and
    Stop
    command
    0:keypad
    1:External
    control
    2:Communicati
    on
    0 ○ When use
    external switch
    on/off, set U0-10=1
    Multi-pump control
  3. Terminal wiring diagram
    In two master and multi slave pumping system,master and standby master drive are connected to
    pressure sensors as below:
    1)Multi-Pump Control-Can realize two masters and Max.4 auxiliaries (standby master works as slave) to
    combine work.
    When display
    smaller than
    gauge,increas e U0-05. When display
    bigger than
    gauge,decreas e U0-05
    9 / 21
    2)There are two masters (one is master,the other is standby master) and 3 slaves. The standby master
    replaces the master to command the whole system only when the master fails to work.The two master
    drives are both equipped with pressure transducers,the other auxiliary drives are without transducers. 3).All the drives are connected through a RS485 Communication line. 4) The master detects pipe water pressure through pressure transducer,and sends the pressure signal
    to the auxiliaries and automatically controls the auxiliaries to run or stop and PID status according to
    the water pressure condition. 5) When master drive failes to work, the standby master will automatically replace the master to controls
    the whole system; when any auxiliary drive fails to work, the system will just skip it by and start the next
    one, ensuring the automatic shift of pump group. 6) The pumps run alternately (8hours by default) to balance every pump’s running time to prolong
    service life of the whole unit machine. 2. Operating steps for multi-pump system
    1) Set target pressure on master drive
    At Stop status, directly press or ( do not need to enter U parameter group)
    and hold for 3 seconds,then set the target pressure.. 2)Set sensor type and sensor range on master and standby drive. Function
    Code
    Description Set range Unit Default Modification
    Level Note
    U0-03 Sensor type
    0: (0-10)
    1: (4-20)
    5: (4-20)
    V
    mA
    mA
    1 ●
    0: V termial
    1: C termial
    5: C1 terminal
    U0-04 Sensor Range 0.0-60 Bar 10 ○ 3)Confirm each pump’s rotation direction
    If any pump’s rotation direction is not correct, refer to one of the following 2 ways to change the the
    rotation direction:
    a. Modify U0-02 value
    b. Exchange any two of U/V/W wiring
    4)Adjust display pressure
    When display smaller than gauge,increase U0-05.When display bigger than gauge,decrease U0-05
    5)Parameters setting for pumping system
    Two pump system :
    Drive type Parameters setting
    Master drive 1 U3-03=2, Standby drive 2 U0-10=2,U0-13=2,U3-01=2
    10 / 21
    Three pump system:
    Drive type Parameters setting
    Master drive 1 U3-03=2
    Standby drive 2 U0-10=2,U0-13=2,U3-01=2,U3-03=2
    Slave drive 3 U0-10=2,U0-13=2,U3-01=3
    Four pump system:
    Drive type Parameters setting
    Master drive 1 U3-03=3
    Standby drive 2 U0-10=2,U0-13=2,U3-01=2,U3-03=3
    Slave drive 3 U0-10=2,U0-13=2,U3-01=3
    Slave drive 4 U0-10=2,U0-13=2,U3-01=4
    Five pump system:
    Drive type Parameters setting
    Master drive 1 U3-03=4
    Standby drive 2 U0-10=2,U0-13=2,U3-01=2,U3-03=3
    Slave drive 3 U0-10=2,U0-13=2,U3-01=3
    Slave drive 4 U0-10=2,U0-13=2,U3-01=4
    Slave drive 5 U0-10=2,U0-13=2,U3-01=5
    Note: The screen display on standby and slave drives are running frequency (default setting)
    Terminal instruction
    Terminal Name Description
    DI1,DI2,D3

Sourcing Information

For quotation, datasheet requests or bulk order inquiries:
- Email: candice@ausenist.com
- WhatsApp: +86 15959950473
- Please provide: exact brand, part number, quantity and application details.

PREVIOUS:E-27 - Industrial Hardware Parts

NEXT:RS485 - Factory Automation Components

Facebook

Twitter

Instagram

Pinterest

LinkedIn

+86-1595995***

candice20114

whatsapp

ausenist@ausenist.com

137651048