d-21 - Industrial Hardware Parts
Part List
U3-12 Carrier Frequency 1-12
6 ● U3-13 Torque Enhancement 0-20.0 % 4.0 ● Depending on
motor
U3-14
Low Frequency Vibration
Suppression Intensity
0-100
100 ○ U3-15 High Frequency Vibration
Suppression Intensity
0-100
0 ○ U3-16
The Turning Point
Between Low & High
Frequency
5.00-50.00
Hz 20.00 ● U3-19 Sleeping Delay Time 1.0-200.0
s 1.0 ○ U3-20 Proportionality Factor 0.0-50.0 10.0 ○ U3-21
Integral Time 0.1-100.0
s 0.6 ○ U3-29
Effective Selections For
Multifunctional Input
Terminal
0: Regular
1: Low effective 0 ● U3-30
Inspection Value For
Feedback Line Broken
0.0-100.0 % 5.0
U3-31 Time For Recognizing
Feedback Line Broken
0.0-3000.0
s 10.0 ○
0.0 represents
do not recognize
U3-32
Motor type 0: asynchronous
1:Permanent
magnet
synchronous
0 ● U3-33 Motor Rated Power 1-1000 KW ● Depending on
motor type
U3-34 Motor Rated Rotation
Speed
1-10000
rpm ● Depending on
motor type
U3-35 Motor Rated Voltage 1-800 V ● Depending on
motor type
U3-36 Motor Rated Current 0.1-1000.0 A ● Depending on
motor type
U3-37 Motor Rated Frequency 5.00-200.0 Hz ● Depending on
motor type
U3-38 Output Phase loss
Protection Selection
0: OFF
1: ON
1 ○ U3-40 Motor Overload Gain
Protection
20.0-1000.0 % 100.0 ○ U3-41 Quick current limit 0: OFF
1: ON
1 ○ U3-42 Overvoltage (stall speed)
Protection Voltage
120-150 % 130 ○ U3-43 Overcurrent Stall Speed
Gain
0-100.0
s 20 ○ U3-44 Overcurrent (stall
speed)Protection Current
100.0-200.0 % 160 ○ U3-45
Low Voltage Protection
Current
70.0-100.0 % 100.0 ○ U3-46 Auto Fault Reset times 0-20 3 ○ U3-47 Fault Reset Interval Time 0.1-100.0 s 10.0 ○ U3-54 Sleep Section
0: OFF
1:ON
1 ●
20 / 21
U3-55
Input phase loss
protection
0: OFF
1:ON
1 ●
d monitoring parameters group
d-00: Output frequency
d-03: Temperature
d-06: Feedback pressure
d-09:Accumulated power-on time(0- 65535H)
d-12:DI input
d-14:The second fault type
d-17: Current when faults happen
d-20: Fault time
d-21:Feedback pressure when faults
happen
d-01: Output current
d-04: Set pressure-current pressure
d-07:Set speed
d-10: V input voltage value
d-13:The first fault type
d-15:The third fault type
d-18: Bus voltage when fault occur
d-02: Bus voltage
d-05: Set pressure
d-08:Accumulated
running time(0-65535H)
d-11:C input current
value
d-16:Fault frequency
d-19:Internal
Temperature when faults
happen
21 / 21
Sourcing Information
For quotation, datasheet requests or bulk order inquiries:
- Email: candice@ausenist.com
- WhatsApp: +86 15959950473
- Please provide: exact brand, part number, quantity and application details.
Quanzhou Ausenist Technology Co., Ltd